Install new fire panel at location for purposes of detection, notification, sprinkler monitoring, and elevator recall. This work is associated with building permit BLD17-04686.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/2/20191/3/20191/3/2019PPASS
DetailsJim Page
Final fire alarm inspection for core and shell only complete. TI work is in progress under different permits.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection12/27/201812/28/201812/28/2018PFAIL
DetailsJim Page
Did not have basement city approved drawings, horn strobe in basement was inoperable but couldn't tell if it was part of the TI system or part of core and shell.

derik Phone #: ###-####
INSP-Final Inspection12/21/201812/27/201812/27/2018PFAIL
DetailsJim Page
Elevator did not work with recall. Could not test flor flow switches, systems were drained.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten