INSP-Final Inspection | 7/23/2019 | 7/24/2019 | 7/24/2019 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection complete.
Call prior to going Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 5/17/2019 | 5/17/2019 | 5/17/2019 | A | FAIL |
Jim Page
|
|
|
Exterior access control for staiwell doors did not release on general alarm, per IFC access control doors in egress paths need to disable and unlock on general fire alarm.
|
INSP-Final Inspection | 5/14/2019 | 5/17/2019 | 5/17/2019 | A | PART |
Jim Page
|
|
|
Final inspection for all initiating devices complete.
Call prior to going Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 5/14/2019 | 5/16/2019 | 5/16/2019 | A | PART |
Jim Page
|
|
|
All associated fire alarm items for elevator recall/shunt complete. Notification inspection for all areas of building complete. Last remaining items to inspect is initiating devices not associated with the fire sprinkler system.
Call prior to going Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 5/14/2019 | 5/15/2019 | 5/15/2019 | P | PART |
Jim Page
|
|
|
Testing for in-duct smoke detection and HVAC unit shutdown complete.
Call prior to going Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|