Permit Information
Permit NumberFIR18-00191
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 4712 W STATE ST
Project NameTreasure Valley Skate
Customer Number 
ePlanReviewYes
Description
[Treasure Valley Skate TI]
The fire sprinkler scope of work consists of protecting an existing building using NFPA 13. The system has a 6” riser and 4”x 2 ½”x 1 ½” grid. The office area has above and below protection. Although the occupancy is light hazard the system has been designed as Ordinary Hazard 2 to accommodate possible future retail use.

• The underground piping is under permit FIR18-00088.
[BLD17-04695]
The fire sprinkler system is used for building area increase and for fire area. Interior nonstructural demolition work was done under permit BLD17-04501. To convert a former bowling alley to an 20,263 square foot indoor roller skating rink facility. Work is to include interior nonbearing walls, two multi-user toilet rooms upgraded to be accessible to the disabled, a reinforced concrete ramp accessible to the disabled as an accessible route and using geofoam as a filler, a reinforced concrete ramp used for egress and using geofoam as a filler but not necessarily complying as an accessible means of egress, reinforced concrete steps, new roof top HVAC units installed directly above existing glulam girders, floor coverings, millwork, and interior wall finishes. Cooking operations that create grease laden vapors are not allowed within this building. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/30/20185/31/20185/31/2018APASS
DetailsJim Page
Final fire sprinkler inspection complete.

Roy Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro5/3/20185/3/20185/3/2018PDONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauge.

Coordinate with Roy Phone #: ###-#### Inspection requested via web by Christophe Wilson
INSP-Sprinkler Rough-in4/25/20184/26/20184/26/2018APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping complete, approved for cover.