INSP-Final Inspection | 8/14/2018 | 8/16/2018 | 8/16/2018 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 8/8/2018 | 8/8/2018 | 8/8/2018 | P | FAIL |
Troy Cobbley
|
|
|
Pendants are still being installed, missing canopies and ceiling tile.
Jordan Fuger is the contact for this final inspection. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 6/28/2018 | 6/28/2018 | 6/28/2018 | P | PASS |
Troy Cobbley
|
|
|
Rough-in passed. Piping can be covered in the tenant space. Drops are not complete in the Entry way. Tim Frost stated he is ok with the two pendants in the ajoining space not being mounted in a ceiling since there is upright protection.
|
INSP-Sprinkler Rough-in | 6/26/2018 | 6/27/2018 | 6/27/2018 | A | CANC |
Troy Cobbley
|
|
|
The revised drawings are not available yet so Jeff is going to re-schedule for tomorrow morning.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 6/18/2018 | 6/19/2018 | 6/19/2018 | A | FAIL |
Troy Cobbley
|
|
|
Water curtain area piping not installed yet. No small documents on site. Plan modifications are needed to show the additional 90's in the sprinkler mains, branchlines and sprinkler drops of both remote areas. Earthquake bracing model/type installed is not the type used. Earthquake bracing missing or installed in wrong location. Bracing may be exceeding 7' in length. Retaining straps and branchline restraints are missing. The two dry sidewalls show on the plans have been deleted and two pendants installed in their place but are attached to a dry system with no return bends. This dry system piping is not shown on the approved plans. No piping can be covered. I did allow borders to be installed.
Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 6/15/2018 | 6/18/2018 | 6/18/2018 | A | CANC |
Troy Cobbley
|
|
|
Sprinkler contractor was not on site. No inspection performed.
Phone #: ###-#### Inspection requested via web by Stan Beus
|