INSP-Final Inspection | 4/2/2019 | 4/3/2019 | 4/3/2019 | P | PASS |
Jim Page
|
|
|
Final AES inspection complete.
as late in pm as possible - can't have alarms go off during school // Will Phone #: ###-####
|
INSP-Final Inspection | 3/22/2019 | 3/22/2019 | 3/22/2019 | P | FAIL |
Jim Page
|
|
|
Trouble restores with monitoring when a general fire alarm is sent even though fire panel is still in trouble.
Bill Phone #: ###-####
|
INSP-Final Inspection | 3/20/2019 | 3/21/2019 | 3/21/2019 | A | FAIL |
Jim Page
|
|
|
Valve on fire sprinkler system reports out as a trouible, when fire alarm panel is in trouble, each subsequent trouble does not report out until panel is reset.
Bill Phone #: ###-####
|
INSP-Final Inspection | 3/14/2019 | 3/15/2019 | 3/15/2019 | A | FAIL |
Jim Page
|
|
|
AES did not show NETCON 5.
Jacob Phone #: ###-####
|
INSP-Final Inspection | 3/14/2019 | 3/14/2019 | 3/14/2019 | P | FAIL |
Jim Page
|
|
|
Put panel into trouble, trouble signal was recieved at central station, sent a general alarm and trouble restored at central station. Issue needs to be resloved and panel needs to be tested with real events and not shorting contacts.
Jacob Phone #: ###-####
|