Permit Information
Permit NumberFIR18-00326
StatusFinaled
Name APEX INTEGRATED SECURITY SOLUTIONS
Site Address 12302 W EXPLORER DR
Project NameSW Idaho Electrical Training
Customer Number 
ePlanReviewYes
Description
Direct replacement of existing fire alarm system panel. This work is associated with building permit BLD18-00561 / project PRJ18-02650.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled  11/25/2019 DONE
INSP-Final Inspection6/6/20186/6/20186/6/2018PCANC
DetailsTroy Cobbley
Still waiting on the outcome of the as-built plans.

As late as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Final Inspection6/4/20186/5/20186/5/2018AFAIL
DetailsTroy Cobbley
Will be ok to final when the as-builts have been accepted.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Final Inspection6/3/20186/4/20186/4/2018AFAIL
DetailsTroy Cobbley
For todays inspection I went through equipment and verified notification device spacing. The candella needs to be changed on several devices and atleast two devices added. We need to test the notification circuit, sprinkler devices and duct smoke detectors. As-builts will be needed as well.

Phone #: ###-#### Inspection requested via web by Nathan Price