Permit Information
Permit NumberFIR18-00332
StatusFinaled
Name STATEFIRE DC SPECIALTIES
Site Address 117 S 10TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Cooking Hood Fire Extinguishing System: Install a 3 gallon Ansul R-102 fire suppression system at Neckar Coffee.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled  11/20/2019 DONE
Kitchen hood was actually removed prior to occupancy. System was fully tested on 3/5/19 and accepted during FIR18-00214 acceptance test.
INSP-Final Inspection5/24/20185/25/20185/25/2018PPART
DetailsJim Page
Operational inspection for ductless hood fire suppression system complete, interface with fire alarm panel will be completed when core and shell fire alarm upgrade is complete. Permit will remain in issued status until fire alarm interface inspection completion.

Dave Phone #: ###-####
INSP-Final Inspection5/24/20185/24/20185/24/2018PFAIL
DetailsJim Page
Fan and lights in cooking area of hood did not shut down on fire system activation.
INSP-Conference4/30/20184/30/20184/30/2018PDONE
DetailsJim Page
Fire conference complete, manual pull for hood system will be installed on south wall as discussed.