Permit Number | FIR18-00402 |
Status | Finaled |
Name |
ABSOLUTE FIRE PROTECTION
|
Site Address |
1111 W JEFFERSON ST Unit: 60
|
Project Name | Boise Plaza Basement Vanilla A |
Customer Number | |
ePlanReview | Yes |
Description |
[Boise Plaza Basement Vanilla]
The fire sprinkler scope of work consists of plugging 11 SSP and relocate 32 SSP using 72" VICFLEX. Calculations provided for 46' equivalent length. Light Hazard office shell.
[BLD18-01455]
(Vanilla SUITE #60– LOWER FLOOR) (3 PERMITS FILED UNDER BLD18-01397 IN EPLANREVIEW) NO OCCUPANCY ALLOWED UNDER THIS PERMIT. TENANT SHALL APPLY FOR CERTIFICATE OF OCCUPANCY PRIOR TO OCCUPYING THE SPACE. This building is fire sprinklered because it is a high rise. Permit is to remodel an existing 3,530 sq. ft. vacant tenant space on the lower plaza level that was created under BLD18-00825 with the creation of the new corridor to the elevator lobby. Approval is contingent upon adhering to the approved plans on file. Work to include: removal of select interior nonbearing walls, removal of select door/door frames, removal of select millwork, removal of select plumbing fixture, select new interior corridor storefront windows, select new suspended acoustic ceiling, select new light fixtures, electrical work and interior finishes in compliance with Ch. 8 of the current IBC. This building is fully Fire Sprinklered. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Alternative Materials and Methods:
• There are no AMM at this time.
|