Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR18-00455
StatusFinaled
Name APEX INTEGRATED SECURITY SOLUTIONS
Site Address 8000 S FEDERAL WAY
Project NameMicron Building 37
Customer Number 
ePlanReviewYes
Description
New Building Fire Alarm Installation. System includes full notification, elevator recall, sprinkler monitoring and duct detection. This work is associated with building permit BLD18-01064. Plan Modification 11-8-18 includes minor changes to floor plan and notification.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/25/20191/25/20191/25/2019PPASS
DetailsTroy Cobbley
Permit finaled

Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
INSP-Alarm Testing1/24/20191/25/20191/25/2019ADONE
DetailsTroy Cobbley
I retested all three elevator lobby detectors for recall, the remaining manual pull stations and all of the flow switches and tamper switches.


Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
INSP-Alarm Testing1/23/20191/24/20191/25/2019PDONE
DetailsTroy Cobbley
Lee witnessed testing of the audio/visuals and smoke dampers.

Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Froese
INSP-Alarm Testing1/2/20191/2/20191/2/2019PPART
DetailsJim Page
Fire alarm testing for level 2 complete except for gym area, gym area to be tested at a later date.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Alarm Testing12/28/201812/28/201812/28/2018PFAIL
DetailsJim Page
Provide3 notification in area between offices on southwest corner. Provide correct coverage in restrooms, currently restrooms have shadow issues. Clean up wiring on NAC panels, can't have wires hanging out of panel.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Alarm Testing12/27/201812/28/201812/28/2018ACANC
DetailsJim Page
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Friday, December 28, 2018.
INSP-Alarm Testing12/17/201812/17/201812/17/2018PPART
DetailsTroy Cobbley
Phase 1 fire alarm work is complete.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Final Inspection12/17/201812/17/201812/17/2018PPART
DetailsTroy Cobbley
Phase 1 fire alarm work complete. The smoke detectors for elevator return now send alarm not supervisory signals.

Adam Phone #: ###-####
INSP-Final Inspection12/14/201812/14/201812/14/2018APART
DetailsJim Page
Fire alarm inspection for level 3 and level 1 lobby complete, fire sprinkker monitoring complete to include standpipe valve supervision. Still need to inspect levels 1 and 2 including pedestrian link.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Alarm Testing12/12/201812/13/201812/13/2018AFAIL
DetailsTroy Cobbley
The inspection today was just for the third floor. Need horn added in the southwest corner. Need strobe in the Executive Break Room. Need all tampers and flow switches tested that effect the third floor and exit pass. Need elevators tested. Need plan mods showing address changes and different NAC panels being used.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Final Inspection12/12/201812/12/201812/12/2018PPART
DetailsJim Page
RTU shutdown testing complete, in-duct detectors tested on levels 2 and 3. Still need to test A/V devices and initiating devices for phase 1 TCO requested areas.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Conference12/10/201812/11/201812/11/2018ADONE
DetailsJim Page
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price.

On site to review 2nd and 3rd floor strobe placement changes. No problems found. No tests performed.
INSP-Alarm Testing12/7/201812/7/201812/7/2018AFAIL
DetailsJim Page
Correct overspacing issues throughout level 3. Verify correct candela settings with city approved drawings. Numerous devices have the candele setting incorrect, candela settings need to match city approved drawings. A re-submittal will be required if devices are added to the fire alarm system that is not on the city approved drawings, to include candela adjustment outside of what is shown on city approved drawings. Correct shadowing issues that are throughout level 3. Correct overspacing issues with level 1 lobby A/V devices.



Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price