Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR18-00495
StatusFinaled
Name IRIDIUM PROCTECTION LLC
Site Address 140 N 16TH ST
Project NameKBOI
Customer Number 
ePlanReviewYes
Description
[KBOI]
The scope of work consists of protecting two enclosures. One enclosure also has a ceiling area. The other enclosure has a raise floor area. Four smoke detectors and four nozzles will be utilized.

? NOTICE:
If this building is fully protected by a fire sprinkler system, then sprinklers are required in both rooms.

[BLD]
There does not seem to be an associated building permit at this time.

Alternative Materials and Methods:

There are no AMM at this time.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/31/20192/1/20192/1/2019APASS
DetailsJim Page
Final inspection for clean agent system complete.

On Site Tech Jeremy Egbert - ###-#### Inspection requested via web by Eric Stanley
INSP-Sprinkler Rough-in/Hydro1/23/20191/28/20191/28/2019AFAIL
DetailsJim Page
Smoke detectors in server room are to close to HVAC registers, need a minimum of 36 inshes from air flow edge to smoke detectors. Verify allowed clearance around nozzles as well as distance from wall.

.

Jeremy Phone #: ###-####