INSP-Final Inspection | 10/30/2019 | 10/30/2019 | 10/30/2019 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 10/28/2019 | 10/29/2019 | 10/29/2019 | P | FAIL |
Troy Cobbley
|
|
|
Changes verified. Plan mods are needed showing the missing detector at first floor elevator lobby and the three NAC panels that are paired with the three other NAC panels. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 10/24/2019 | 10/25/2019 | 10/25/2019 | P | CANC |
Jim Page
|
|
|
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
|
INSP-Final Inspection | 10/24/2019 | 10/25/2019 | 10/24/2019 | A | CANC |
Troy Cobbley
|
|
|
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
|
INSP-Alarm Testing | 10/9/2019 | 10/10/2019 | 10/10/2019 | P | DONE |
Troy Cobbley
|
|
|
Tested the remaining smoke detectors and elevator recall. Per Lee the volume of the horns has been verified by a third party and is ok. Items need prior to a final sign off are the sync issue with the horns and the previously noted changes need to be applied. Plan mods are needed showing all of the changes.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Alarm Testing | 10/9/2019 | 10/9/2019 | 10/9/2019 | P | DONE |
Troy Cobbley
|
|
|
Todays inspection we tested the smoke detectors in the first floor central area and the north wing. All tested ok. We set off the notification for the entire building and I noted that the visual devices have two patterns which is ok but the audible devices do not sync which is not ok as per NFPA 72. Also the smoke detectors are reporting correctly. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Alarm Testing | 10/4/2019 | 10/4/2019 | 10/4/2019 | P | FAIL |
Troy Cobbley
|
|
|
The smoke detectors are not reporting to the facp. Inspection stopped. The receiver troubles have been cleared.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Alarm Testing | 10/1/2019 | 10/2/2019 | 10/2/2019 | P | DONE |
Troy Cobbley
|
|
|
Today we finished the building walk through for the notification appliances. See the city approved plans for locations of deficiencies. Approx. 30 items. The fire alarm panel currently has dial out issues and does not appear to be reporting signals. Plans need to be resubmitted showing the candella changes and that many of the smoke detectors have not been installed. No smoke detectors were tested due to the communication troubles on the fire alarm panel.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 9/30/2019 | 10/1/2019 | 10/1/2019 | A | FAIL |
Troy Cobbley
|
|
|
For todays inspection I was able to check spaqcing of the south wing and center section first floor. Several devices are overspaced and many more had the candellas set incorrectly. Plans do not match the install such as horns shown but horn/strobes installed (the horn/strobes are required) Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 9/13/2019 | 9/16/2019 | 9/16/2019 | A | FAIL |
Troy Cobbley
|
|
|
Audibility levels tested. Most areas exceeded the maximum allowable volume of 110 dB and peaked between 112 and 116. All areas need to be reduced to below 110 dB. jonathan Phone #: ###-####.
|
INSP-Alarm Testing | 7/11/2019 | 7/12/2019 | 7/12/2019 | A | DONE |
Troy Cobbley
|
|
|
Todays inspection we verified phone lines, panel, duct detector/hvac unit shutdown, flow switches and tamper switches. Plan modifications are needed showing all of the changes. Strobes are over spaced and need to be relocated or the candella adjusted. Smoke detectors are too close to diffusers. Strobes are missing in on location on the second floor as marked on the plans. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Conference | 2/28/2019 | 3/4/2019 | 3/4/2019 | A | DONE |
Troy Cobbley
|
|
|
I went over smoke detector spacing with the electrical and fire alarm contractor. I deferred elevator recall requirement to state inspector.
Contact Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|