Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR18-00569
StatusFinaled
Name WEBSTER FIRE PROTECTION
Site Address 13255 W MCMILLAN RD
Project NamePioneer Elementary
Customer Number 
ePlanReviewYes
Description
Adding initiation, duct detection and voice notification to an existing fire alarm system in an existing building with new classrooms and a new gymnasium. This work is associated with building permit BLD18-01190.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/1/20191/2/20191/2/2019APASS
DetailsTroy Cobbley
Permit finaled

Phone #: ###-#### Inspection requested via web by Ken Webster
INSP-Final Inspection12/27/201812/28/201812/28/2018AFAIL
DetailsTroy Cobbley

Need as-builts/plan mods for all of the candella changes, need to discuss Entry way notification with plan review and add if required, need weather proof backbox in Dishwashing area on the speaker strobe, need to verify phone lines, need to verify equipment and batteries, need to verify dedicated circuit, need to verify function of notification.


Ken Phone #: ###-####
INSP-Alarm Testing12/17/201812/18/201812/18/2018ADONE
DetailsTroy Cobbley
The testing of the fire smoke dampers performed today. One is no-functional and will need to be re-tested.

Buck-partial Phone #: ###-####
INSP-Alarm Testing12/13/201812/14/201812/14/2018ADONE
DetailsTroy Cobbley
Today we tested the second duct smoke detector that failed to work yesterday. Today it functioned correctly.

inspecting in -ducts in Pioneer gym Phone #: ###-#### Inspection requested via web by Ken Webster
INSP-Alarm Testing12/12/201812/13/201812/13/2018APART
DetailsTroy Cobbley
Only the four fire smoke dampers and the east side duct detector were tested today in the Gym. The west side hvac unit did not function.

Phone #: ###-#### Inspection requested via web by Ken Webster