Permit Information
Permit NumberFIR18-00630
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 11522 W FAIRVIEW AVE
Project NameDaVinci Stone Fire Alarm
Customer Number 
ePlanReviewYes
Description
Fire alarm scope is to install a new fire alarm system to monitor the new fire sprinkler system. This work is associated with building prmit BLD17-04590.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/2/20191/4/20191/4/2019APASS
DetailsTroy Cobbley
Permit finaled

John Howard, Technician Phone #: ###-#### Inspection requested via web by John Siewert
INSP-Final Inspection12/20/201812/21/201812/21/2018AFAIL
DetailsJim Page
Flow switch did not operate with water flow, FDC bell stopped when panel was silenced, did not continue to ring with flow switch being held, FDC bell needs to ring during water flow.

John Howard, Technician Phone #: ###-#### Inspection requested via web by John Siewert