Permit Information
Permit NumberFIR18-00642
StatusFinaled
Name APEX INTEGRATED SECURITY SOLUTIONS
Site Address 6280 N EAGLE RD
Project NameTarget Boise NW
Customer Number 
ePlanReviewYes
Description
Target Boise NW Fire alarm replacement on existing building. This work does not appear to be associated with a building permit. Plan modification 10-16-2018 to add notification in areas that do not appear to have been adequately covered in the previous design.Plan modification 1-28-19. Corrections noted during inspections.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/6/20194/8/20194/8/2019APASS
DetailsJim Page
Previously noted items have been corrected, final fire alarm inspection complete.

As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Final Inspection2/13/20192/14/20192/14/2019AFAIL
DetailsTroy Cobbley
The hvac units did not shut down upon alarm activation as required per IMC 606.4, need the enclosure for the communicator installed.

As early as possible Phone #: 2088308262 >> Inspection requested via mobile web by Tip Ioane
FIR-Aging Inspection2/13/20192/13/20192/13/2019AFAIL
DetailsTroy Cobbley
Not ready for final due to issues with hvac activation, need protecive cover for IP DACT, need cut sheet for FACP showing internal mounting for IP DACT, need fuel verification for generator, need to verify as-builts are correct (NAC's)
INSP-Final Inspection2/12/20192/13/20192/13/2019ACANC
DetailsTroy Cobbley
As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Wednesday, February 13, 2019.
INSP-Final Inspection2/4/20192/7/20192/7/2019ACANC
DetailsTroy Cobbley
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Final Inspection1/24/20191/31/20191/31/2019AFAIL
DetailsTroy Cobbley
Todays inspection included verifying candellas for the audio/visuals, fire sprinkler risers and smoke detector door release. We were unable to test hvac shutdown due to Target Policy. Plan modifications are required showing the changes strobes, NAC panels, addressing and means of communication. Note IP DACT is installed inproperly and not shown on the plans or battery calcs.


As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Final Inspection1/21/20191/24/20191/24/2019ADONE
DetailsTroy Cobbley
As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price.

3:30 pm test is too late for Target. Nathan cancelled.
INSP-Final Inspection1/21/20191/22/20191/21/2019ACANC
DetailsTroy Cobbley
As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Monday, January 21, 2019.
INSP-Final Inspection11/26/201811/27/201811/27/2018AFAIL
DetailsTroy Cobbley
Todays inspection was just for the notification devices. See the city approved plans for the devices overspaced or mounted too high. Not all of the devices have been checked for the correct candella. Contractor will need to contact plan review on whether a plan mod is needed or just as-builts. Also the fire doors did not close when the smoke detectors were tested.


Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Conference9/26/20189/27/20189/27/2018ADONE
DetailsTroy Cobbley
We dicussed obstructions to the strobes in the Store Room areas.

As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price