Permit Information
Permit NumberFIR18-00690
StatusFinaled
Name JOHNSON CONTROLS FIRE PROTECTION
Site Address 4455 E WARM SPRINGS AVE
Project NameAspen Valley Senior Living
Customer Number 
ePlanReviewYes
Description
Provide and install a new automatic and manual fire alarm system with sprinkler monitoring, in room system detectors with sounder bases, corridor detection and full notification in common areas. This work is associated with building permit BLD18-00494.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/20/20195/20/20195/20/2019PPASS
DetailsJim Page
Final fire alarm inspection complete.

please have this aft 3:00 pm if possible call joe 30 min prior to inspect ###-#### Phone #: ###-#### Inspection requested via web by Kristin Dolan
INSP-Final Inspection5/9/20195/10/20195/10/2019APART
DetailsMark Scharfen
Tested system. TCO of 10 days granted to verify 6 corrections. Approved by Ron Johnson

ada room strobes do not turn off until reset.
sounders in rooms 101, 107, 118 sound steady (bad base).

2 smokes in beam pockets to be lowered to bottom of beam (greater than .1 less than .4)



Phone #: ###-#### Inspection requested via web by Kristin Dolan
INSP-Final Inspection5/7/20195/8/20195/8/2019AFAIL
DetailsMark Scharfen
Checked candella and smoke placment. Tested sprinkler interconnect and cell monitoring. While testing C wing found several problems:

Sounder bases in room will not resound alarms.
Room 309 bedroom strobe failed.
no ac labels on fire or nac panels.
Cell Dact needs to be added to fire alarm drawing and submitted as an as-build.
access control doors do not drop on fire alarm.

Did not verify horn strobe functionality in rest of building.

Still need to test majority of smoke detectors, CO detectors, access control interface, majority of notification devices.

Please call when in route. We are finalling sprinkler and FA at the same time. Phone #: ###-#### >> Inspection requested via web by Kristin Dolan