DOC - Permit Finaled | | | 6/13/2019 | | DONE |
|
|
|
Final acceptance test passed 6-6-19 and as builts approved 6-13-19.
|
INSP-Final Inspection | 6/3/2019 | 6/4/2019 | 6/6/2019 | P | FAIL |
Troy Cobbley
|
|
|
Permit will be ok for final when as-builts are approved.
Ray McQueen, inspecting technician Phone #: ###-#### Inspection requested via web by Rose Peterson
|
INSP-Final Inspection | 3/26/2019 | 3/28/2019 | 3/28/2019 | A | FAIL |
Troy Cobbley
|
|
|
Resubmit plans that show entire scope of work that includes all devices in all buildings. Devices shall annunciate by the building address. Installation shall meet NFPA 72. Provide updated battery and notification circuit calculations. Separate remote annunciators maybe required for each building. Lightning protection may be required for circuits connecting each building. All buildings may require riser room pull stations. The horns on the exterior of the building may not be required.
Ray McQueen, inspecting technician Phone #: ###-#### Inspection requested via web by Rose Peterson
|
INSP-Final Inspection | 1/24/2019 | 1/30/2019 | 1/30/2019 | A | CANC |
Troy Cobbley
|
|
|
Cancel per Ray McQueen, inspecting technician Phone #: ###-#### Inspection requested via web by Rose Peterson
|
INSP-Final Inspection | 12/28/2018 | 1/4/2019 | 1/2/2019 | A | CANC |
Troy Cobbley
|
|
|
Ray McQueen, inspecting technician Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
|
INSP-Final Inspection | 10/4/2018 | 10/9/2018 | 10/8/2018 | A | CANC |
Troy Cobbley
|
|
|
Ray McQueen, inspecting technician, building access is open Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
|