INSP-Final Inspection | 7/3/2019 | 7/3/2019 | 7/3/2019 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
INSP-Alarm Testing | 6/17/2019 | 6/17/2019 | 6/17/2019 | P | DONE |
Troy Cobbley
|
|
|
The interconnections with the fire pump have been tested. For a final the interconnection with the elevator needs tested.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
INSP-Sprinkler Rough-in/Hydro | 6/17/2019 | 6/17/2019 | 6/17/2019 | P | CANC |
Troy Cobbley
|
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Monday, June 17, 2019.
|
INSP-Alarm Testing | 6/14/2019 | 6/17/2019 | 6/17/2019 | A | CANC |
Troy Cobbley
|
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
INSP-Final Inspection | 6/14/2019 | 6/14/2019 | 6/14/2019 | P | CANC |
Troy Cobbley
|
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Friday, June 14, 2019.
|
INSP-Alarm Testing | 6/7/2019 | 6/7/2019 | 6/7/2019 | P | DONE |
Troy Cobbley
|
|
|
Need the interconnections with the fire sprinkler/fire pump devices tested, need elevator recall tested. Need duct smoke detectors tested. It appears the sync issue is actually an echo from the concrete floors and large open spaces. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
INSP-Alarm Testing | 6/6/2019 | 6/7/2019 | 6/7/2019 | A | CANC |
Troy Cobbley
|
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Friday, June 07, 2019.
|
INSP-Final Inspection | 6/6/2019 | 6/6/2019 | 6/6/2019 | P | FAIL |
Troy Cobbley
|
|
|
The fire alarm interconnection with the fire pump devices was not ready. We set off the notificatoin circuit and found that the audio portion is not syncing. Yesterdays correction noted have been addressed.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
INSP-Alarm Testing | 6/6/2019 | 6/7/2019 | 6/6/2019 | P | CANC |
Troy Cobbley
|
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Thursday, June 06, 2019.
|
INSP-Alarm Testing | 6/3/2019 | 6/4/2019 | 6/4/2019 | P | DONE |
Troy Cobbley
|
|
|
Nathan and I did a walk through. I verified notification device placement and noted several areas where they need to be relocated and/or added. I also verified the FACP/NAC/Dialer model. No actual test could be performed due to the sprinkler system keeping the FACP busy with signals at this time. No elevator has been installed yet. As-builts will be required per our conversation prior to a final testing.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|