Permit NumberFIR18-00809
StatusFinaled
Name APEX INTEGRATED SECURITY SOLUTIONS
Site Address 12251 W FRANKLIN RD
Project NameCJD Investments LLC - FA
Customer Number 
ePlanReviewYes
Description
This is a parts and smarts Fire Alarm design for CJD Investments. Work is to include a sprinkler monitoring system, fire pump monitoring, elevator recall and shunt with full audible and visible notification. This work is associated with building permit BLD18-02795.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/3/20197/3/20197/3/2019PPASS
DetailsTroy Cobbley
Permit finaled

Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
INSP-Alarm Testing6/17/20196/17/20196/17/2019PDONE
DetailsTroy Cobbley
The interconnections with the fire pump have been tested. For a final the interconnection with the elevator needs tested.

Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
INSP-Sprinkler Rough-in/Hydro6/17/20196/17/20196/17/2019PCANC
DetailsTroy Cobbley
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Monday, June 17, 2019.
INSP-Alarm Testing6/14/20196/17/20196/17/2019ACANC
DetailsTroy Cobbley
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
INSP-Final Inspection6/14/20196/14/20196/14/2019PCANC
DetailsTroy Cobbley
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Friday, June 14, 2019.
INSP-Alarm Testing6/7/20196/7/20196/7/2019PDONE
DetailsTroy Cobbley
Need the interconnections with the fire sprinkler/fire pump devices tested, need elevator recall tested. Need duct smoke detectors tested. It appears the sync issue is actually an echo from the concrete floors and large open spaces.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
INSP-Alarm Testing6/6/20196/7/20196/7/2019ACANC
DetailsTroy Cobbley
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Friday, June 07, 2019.
INSP-Final Inspection6/6/20196/6/20196/6/2019PFAIL
DetailsTroy Cobbley
The fire alarm interconnection with the fire pump devices was not ready. We set off the notificatoin circuit and found that the audio portion is not syncing. Yesterdays correction noted have been addressed.

Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
INSP-Alarm Testing6/6/20196/7/20196/6/2019PCANC
DetailsTroy Cobbley
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Thursday, June 06, 2019.
INSP-Alarm Testing6/3/20196/4/20196/4/2019PDONE
DetailsTroy Cobbley
Nathan and I did a walk through. I verified notification device placement and noted several areas where they need to be relocated and/or added. I also verified the FACP/NAC/Dialer model. No actual test could be performed due to the sprinkler system keeping the FACP busy with signals at this time. No elevator has been installed yet. As-builts will be required per our conversation prior to a final testing.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price