Permit Information
Permit NumberFIR18-00835
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 1299 N ORCHARD ST
Project NameOrchard Bank FA Improvements
Customer Number 
ePlanReviewYes
Description
Replace existing fire alarm system control panel, power supplies, initiating and notification devices. Improvement will reuse existing fire alarm wiring circuitry and match existing conductor size and color where modified or extended.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled  11/20/2019 DONE
All requested documentation received and approved.
INSP-Final Inspection4/11/20194/12/20194/12/2019AFAIL
DetailsTroy Cobbley
Permit will be ok to final when documents are provided to plan review that address the supervisory/rrouble on panel as per revios corretion


John Howard, Technician Phone #: ###-#### Inspection requested via web by John Siewert
INSP-Final Inspection2/28/20193/1/20193/1/2019AFAIL
DetailsTroy Cobbley
See the city approved plans for a list of required corrections.


Earl Lasater, Technician Phone #: ###-#### Inspection requested via web by John Siewert
FIR-Aging Inspection2/28/20192/28/20192/28/2019PCANC
DetailsTroy Cobbley
Wrong inspection type called in.
INSP-Alarm Testing2/28/20192/28/20192/28/2019PDONE
DetailsTroy Cobbley
Earl and I did a walk through of the Basement, first floor and second floor corridor system and verified horn/strobe spacing/height.
INSP-Final Inspection1/15/20191/16/20191/16/2019PFAIL
DetailsTroy Cobbley
No testing of devices performed today. Inspection was only for the Basement area. Plan modifications are needed showing the correct form of communication, fire sprinkler riser device count (delete dry system), strobes are too low, wall and ceiling mount devices do not corrispond with the plans, Storage Room needs notification device modifications, batteries in the FACP do not match plans. We discussed the function of the Basement duct smoke detectors in the Mechanical Room.

Earl Lasater, Technician Phone #: ###-#### Inspection requested via web by John Siewert