Permit Information
Permit NumberFIR18-00923
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 705 S 8TH ST
Project NameBIOMARK OFFICE TI
Customer Number 
ePlanReviewYes
Description
[ Quick Permit]***SHILO WILL ADD 2 TYCO 5.6K PENDENT SPRINKLERS TO A NEWLY FRAMED OFFICE AREA IN AN EXISTING BUILDING. THE AREA WAS PREVIOUSLY PROTECTED BY UPRIGHT SPRINKLERS AT THE DECK. WITH THE ADDITION OF THE CEILING, PENDENT SPRINKLERS MUST BE INSTALLED.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/2/20191/3/20191/3/2019APASS
DetailsJim Page
Final fire sprinkler inspection for area of work complete.

Jim Baker is the contact Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in1/2/20191/3/20191/3/2019APASS
DetailsJim Page
Previously noted items have been corrected, rough to cover inspection complete, approved for cover.

Jim Baker is the contact Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection12/27/201812/27/201812/27/2018PCANC
DetailsJim Page
Project did not pass rough in inspection, not ready for final, this request is cancelled.

Contact is Jim Baker Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in12/27/201812/27/201812/27/2018PFAIL
DetailsJim Page
Fire sprinkler heads are overspaced in area of work, corrections are needed.

Contact is Jim Baker Phone #: ###-#### Inspection requested via web by Stan Beus