DOC - Permit Finaled | | | 9/17/2019 | | DONE |
|
|
|
All testing complete.
|
INSP-Final Inspection | 9/16/2019 | 9/16/2019 | 9/16/2019 | P | PASS |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by Ken Webster
Tested duct detectors and fan shutdown. All functioned properly. Verified all detectors previously too close to HVAC registers had been moved.
|
INSP-Final Inspection | 9/11/2019 | 9/12/2019 | 9/12/2019 | P | FAIL |
Jim Page
|
|
|
All audio visual devices have been inspected, all fire sprinkler related items have been inspected with no deficiencies. 6 Smoke detectors in daycare area are within 36 inches of HVAC registers, smoke detectors have to be a minimum of 36 inches away from HVAC registers.
Fire Alarm Final Phone #: ###-#### Inspection requested via web by Ken Webster
|