INSP-Final Inspection | 3/12/2019 | 3/15/2019 | 3/15/2019 | A | PASS |
Jim Page
|
|
|
Please contact nate roughly 15 mins to arrival Phone #: ###-#### >> Inspection requested via web by jason petty
Verified all outstanding items were met.
|
DOC - Permit Finaled | | | 3/15/2019 | | DONE |
|
|
|
|
INSP-Final Inspection | 3/6/2019 | 3/6/2019 | 3/6/2019 | A | FAIL |
Troy Cobbley
|
|
|
Tested 100% panel functionality. Sprinkler monitoring, initiaing and notification devices. Passed test. Still need updated addresses on as-built plans and building map, AC breaker lock. There was mention of access control being added before buillding is completed. Basement has a kitchen with residential hood. Class one hood may need to be added.
Nate with Peak was on site.
|
INSP-Final Inspection | 3/4/2019 | 3/5/2019 | 3/6/2019 | P | FAIL |
Troy Cobbley
|
|
|
Tested 100% panel functionality. Sprinkler monitoring, initiaing and notification devices. Passed test. Still need updated addresses on as-built plans and building map, AC breaker lock. There was mention of access control being added before buillding is completed. Basement has a kitchen with residential hood. Class one hood may need to be added.
Please call Nate roughly 15 minutes prior to arrival. Phone #: ###-#### Inspection requested via web by jason petty
|
INSP-Final Inspection | 2/18/2019 | 2/20/2019 | 2/20/2019 | P | FAIL |
Troy Cobbley
|
|
|
No actual testing performed. Plan mods are needed showing the actual fire alarm panel installed, a smoke detector is needed over the facp, provide verification whether hvac shutdown is needed or not, provide plan mods or make field changes to strobes that are overspaced, provide device map as per the review comments.
Nate Schneider is point of contact, please call roughly 15 minutes prior to arriving to site. ###-#### Phone #: ###-#### Inspection requested via web by jason petty
|