Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR19-00080
StatusFinaled
Name PROTEX
Site Address 2121 N COLE RD
Project NameFairmont Panel Replacement
Customer Number 
ePlanReviewYes
Description
Upgrade existing fire alarm control panel to voice and add additional building devices. This is a stand alone building that is not connected to the main building. This work is associated with building permit BLD18-00943.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/12/20196/13/20196/13/2019PPASS
DetailsTroy Cobbley
Permit finaled

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection6/4/20196/5/20196/5/2019AFAIL
DetailsTroy Cobbley
Plan mod needed for changing the hallway strobes to 30cd, need to show Mezzanine and Mechanical Room notification devices, need to test Gym duct smoke detectors and change two devices to weather proof. Need to witness notification testing.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection3/21/20193/22/20193/22/2019PPART
DetailsTroy Cobbley
Phase 1 fire alarm complete. See comments by Lee for items needing correcting from the Phase 1 inspection prior to a final fire alarm permit sign off.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection3/20/20193/21/20193/21/2019PFAIL
DetailsTroy Cobbley
Not all of the plan package on site, drawings (facp, amp not same as drawings) no dialer shown, smoke over facp too low. No testing performed.


Partial Final for cafeteria and commons. Dirk is Contact. Phone #: ###-#### Inspection requested via web by Morgan Ahten