Permit Information
Permit NumberFIR19-00112
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 1215 W STATE ST
Project NameState Insurance Fund FA
Customer Number 
ePlanReviewYes
Description
Replacement of existing fire alarm control panel and initiating devices. Full upgrade of A/V occupant notification. This work does not appear to be associated with a building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/9/20197/11/20197/11/2019APASS
DetailsJim Page
Previously noted items have been corrected, final fire alarm inspection complete.

Requesting inspection at 7AM. John Howard, Technician Phone #: ###-#### Inspection requested via web by John Siewert
INSP-Final Inspection6/26/20197/3/20197/3/2019ACANC
DetailsJim Page
Inspection request will be rescheduled per conversation with point of contact, the 7AM inspection time was not cooodinated, need a minimum of a 24 hour notice with my approval as well as my supervisors approval for inspections outside of my normal working hours. Next inspection needs to be coordinated or it will result in a fail, this request is cancelled.

Requesting inspection at 7AM - John Howard, Technician Phone #: ###-#### Inspection requested via web by John Siewert
INSP-Final Inspection6/17/20196/18/20196/18/2019AFAIL
DetailsJim Page
Audio visual device in basement next to print room is blocked by duct work. Sound requirements were no met for basement level restrooms. Adjust/add notification that is blocked on level 2, city approved drawings are notated for areas that require attention.

John Howard Technician, Phone #: ###-#### Inspection requested via web by John Siewert