Permit Information
Permit NumberFIR19-00163
StatusFinaled
Name JOHNSON CONTROLS FIRE PROTECTION
Site Address 325 W IDAHO ST
Project NameSt Lukes DCIP Family Residency
Customer Number 
ePlanReviewYes
Description
Johnson Controls offers this proposal for the St. Luke Health Service DCIP Family Residency fire alarm bid, in Boise, Idaho. The Fire Alarm system proposal is based on Eidam Engineering bid documents issued for the fire alarm system. System design includes full audible and visible notification, sprinkler monitoring, duct detection and a remote annunciator. Central station monitoring with 2 telephone lines. This work is associate with building permit BLD18-03442.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/13/20199/13/20199/13/2019PPASS
DetailsMark Scharfen
passed fire alarm

Call ahead to kristin @ ###-####. Please have inspection 1:30 and on if possible. If its going to be earlier I need to know at least 1 hour in advance so I can find another tech to be onsite. Thank you very very much. Phone #: ###-#### Inspection requested via web by Kristin Dolan
INSP-Final Inspection9/10/20199/11/20199/11/2019AFAIL
DetailsMark Scharfen
Plans do not match what is installed. Plans show two phone lines for monitoring. There is a DSC Cell DACT installed that is not on plans. According to JCI this was installed by Apex. Did not check horn strobe placment/candella. THere is an in duct detector in the reception area that is above hard lid ceiling with no access hatch. Per Brian, he accessed by moving the 120V lighting. I noted there were at least 4 card readers (not live) by entry doors and there is no access control interface shown on fire alarm plans. While access control integration with fire alarm wouldn't hold up fire alarm final it may hold up building life safety. I gave this information verbally to both Damien over the phone and Brian, both with JCI. General Contractor was not on site.

Call ahead to Brian ###-#### Phone #: ###-#### >> Inspection requested via web by Kristin Dolan