Description
This scope of work is to relocate two speaker/strobes and add additional audible devices to accommodate a tenant improvement in Unit 100 on the 1st floor of the Jefferson Building. The existing voice evac system is being modified, but no initiating devices are being affected by this T.I. Visual devices will be connected to existing FACP NAC #3, and the Audible devices will be connected to the existing AMP speaker circuit #3. Visual device candela ratings have been adjusted for ceiling heights over 10'. All ceilings are less than 20' in height. This work is associated with building permit BLD18-04004.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/1/20195/2/20195/2/2019APASS
DetailsMark Scharfen
Conducted fire alarm inspection. Verified device functionality and signals. Passed.

Mike Phone #: ###-####
INSP-Final Inspection4/30/20194/30/20194/30/2019PFAIL
DetailsMark Scharfen
Checked strobe placement and settings. When testing fire alarm the speaker circuit did not activate. Mike with State was going to verify programming and reschedule.