Permit Information
Permit NumberFIR19-00218
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 7564 W VICTORY RD
Project NameWurth Louis TI
Customer Number 
ePlanReviewYes
Description
***QUICK PERMIT**MAS** Add SSP heads throughout the new ceiling grid.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/9/20195/10/20195/10/2019APASS
DetailsTroy Cobbley
Permit finaled

Rick Phone #: ###-#### Inspection requested via web by Nathan Stenquist
INSP-Sprinkler Rough-in5/3/20195/3/20195/3/2019PPASS
DetailsTroy Cobbley
Rough-in passed. Piping can be covered.

Jon O Phone #: ###-#### Inspection requested via web by Nathan Stenquist
INSP-Sprinkler Rough-in/Hydro4/26/20194/26/20194/26/2019PFAIL
DetailsTroy Cobbley
Per the city approved plans the front area is considered an "M" occupancy and will need the pendant heads spaced for ordinary hazard not light hazard. Adam Phone #: ###-####