Permit Information
Permit NumberFIR19-00230
StatusFinaled
Name APEX INTEGRATED SECURITY SOLUTIONS
Site Address 3075 W CRESCENT RIM DR
Project NameCrescent Rim Bldg 1
Customer Number 
ePlanReviewYes
Description
Crescent Rim B1 scope of work is to install a complete addressable Fire Alarm System to an existing building. New slave FACP panel to be connected to existing building 2&3 master FACP for outside alarm supervision. This work is associated with building permit BLD06-02322.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/11/20202/12/20202/12/2020APASS
DetailsTroy Cobbley
Permit finaled. The associated permit FIR20-00069 has been finaled.

Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
INSP-Final Inspection2/6/20202/7/20202/6/2020ACANC
DetailsTroy Cobbley
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Thursday, February 06, 2020.
INSP-Final Inspection2/5/20202/6/20202/6/2020AFAIL
DetailsGreg Ruxton
Permit failed based on noted deficiencies: induct smoke detector descriptors not correct (2nd fl ); basement riser room devices descriptors need to identify devices as being in the basement riser room. Contractor to coordinate with monitoring company to ensure accuracy of descriptors before next inspection. 2088990672 >> Inspection requested via mobile web by Josiah Froese
INSP-Final Inspection1/31/20202/3/20202/3/2020AFAIL
DetailsTroy Cobbley
Permit can be finaled when the permit for the fire alarm panel replacement has been inspected/finaled. Today we verified the two smoke detectors in the Basement Mech Room.

Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
INSP-Final Inspection1/29/20201/29/20201/29/2020PCANC
DetailsTroy Cobbley
Cancel per discussion with Josiah due to issues with the fire alarm panel.

Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
INSP-Alarm Testing1/16/20201/17/20201/17/2020ADONE
DetailsTroy Cobbley
For a final sign off as-builts are needed to be approved and the building shall report out to the monitoring company with the building address for these signals.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
INSP-Alarm Testing1/15/20201/16/20201/17/2020ADONE
DetailsTroy Cobbley
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price

Tested duct detection and fire smoke dampers, elevator recall and shunt, basement thru floor 3 wet sprinklers in stair L, sprinkler bell, manual alarm. All operated properly. Strobes need to be installed in the trash rooms. Centeral station monitoring was not verified and some sprinkler work still needs to be verified. LGM