Permit NumberFIR19-00242
StatusFinaled
Name JOHNSON CONTROLS FIRE PROTECTION
Site Address 300 W FORT ST
Project NameFort Boise School Renovation
Customer Number 
ePlanReviewYes
Description
Modify alarm notification of existing fire alarm system. System is to be expanded as is. New notification is to match existing horn and strobe signals. This work is associated with building permit BLD19-00142.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/7/20198/8/20198/8/2019PPASS
DetailsJim Page
Previously noted except for the sync issue have been corrected, sync repair is being addressed under a seperate permit, FIR19-00588. Final inspection for this scope of work complete.

DEMIAN Phone #: ###-####
INSP-Final Inspection7/29/20198/2/20198/2/2019PCANC
DetailsJim Page
Cnacelled per conversation with point of contact, not ready for final inspection, will be rescheduled for a later date.

Please make last of day inspection, we can''t set off anything until 4:00 on. Phone #: ###-#### Inspection requested via web by Kristin Dolan
INSP-Final Inspection6/24/20196/25/20196/25/2019AFAIL
DetailsJim Page
Notated city approved drawings where sound level requirements were not met per NFPA72. Need to add an A/V device in notated area on city approved drawings. Audio visual devices throughout went out of sync during inspection.

Please call 30 minutes prior. Phone #: ###-#### Inspection requested via web by Kristin Dolan
INSP-Final Inspection5/20/20195/23/20195/23/2019ACANC
DetailsJim Page
Inspection request cancelled per conversation with point of contact, fire panel had troubles that were associated with the fire alarm system that could not be repaired before inspection, this request is cancelled.

Please call 30 minutes prior to inspection - Joe ###-#### Phone #: ###-#### Inspection requested via web by Kristin Dolan
INSP-Final Inspection5/17/20195/20/20195/20/2019ACANC
DetailsJim Page
Cancelled per conversation with point of contact, inspection request was suppose to be for a different day, this request is cancelled at POC request.

Please call Joe prior to coming ###-#### Phone #: ###-#### Inspection requested via web by Kristin Dolan