INSP-Final Inspection | 11/27/2019 | 12/3/2019 | 12/3/2019 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection is complete.
6am per Joe Bruce // Damien Phone #: ###-####
|
INSP-Final Inspection | 11/26/2019 | 11/26/2019 | 11/26/2019 | A | FAIL |
Jim Page
|
|
|
Fire alarm has audio issues with the three temporal, a re-inspection will be required after audio issue is resolved.
###-#### - Damien
|
INSP-Final Inspection | 11/13/2019 | 11/14/2019 | 11/14/2019 | A | FAIL |
Jim Page
|
|
|
City approved drawings have been notated areas that need to be corrected. Relocate dcevices that are overspaced or adjust candella setting. Provide weather proof devices in restrooms that have showers. Add notication in multi-person offices as dicussed.
5am
|
INSP-Final Inspection | 11/7/2019 | 11/7/2019 | 11/7/2019 | P | PART |
Jim Page
|
|
|
Fire alarm inspection for surgical suite, southwest side of building complete to include corridors outside of surgical suite. Remaining areas to be inspected at a later date.
Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
INSP-Final Inspection | 10/24/2019 | 10/24/2019 | 10/24/2019 | P | FAIL |
Jim Page
|
|
|
Relocate smoke detectors that are to close to HVAC registers. Provide weather proof A/V devides in prep area behind surgical suites. Verify if door hold magnets are going to stay in place, if door holds stay then smoke detectors will be required for door release.
Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
INSP-Final Inspection | 10/22/2019 | 10/23/2019 | 10/23/2019 | A | FAIL |
Jim Page
|
|
|
Occupancy is a B occupancy, provide notification in post op and pre op rooms. Relocate notification in areas as discussed. No devices tested.
Call ahead to Damien @ ###-#### Phone #: ###-#### Inspection requested via web by Kristin Dolan
|