Permit Information
Permit NumberFIR19-00268
StatusFinaled
Name JOHNSON CONTROLS FIRE PROTECTION
Site Address 333 N 1ST ST
Project NameSLHS DCIP Surgery Center
Customer Number 
ePlanReviewYes
Description
Provide a new fire alarm system in an existing building remodel. Design of the surgery center includes 100% smoke coverage. Smoke fire dampers are to be activated by full area detection in the surgery center and by in duct detection for remaining areas, magnetic door holders are activated by corridor area coverage in the surgery center and do not require centered detectors within five feet. The remaining floors / areas have corridors that do not have full coverage and are activated by dedicated detectors at door holders. System includes manual alarm stations at all exits and several nurse’s stations, duct detection with HVAC interface, elevator recall and shunt. Notification is to be public mode. This work is associated with building permit BLD18-03657.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/27/201912/3/201912/3/2019APASS
DetailsJim Page
Final fire alarm inspection is complete.

6am per Joe Bruce // Damien Phone #: ###-####
INSP-Final Inspection11/26/201911/26/201911/26/2019AFAIL
DetailsJim Page
Fire alarm has audio issues with the three temporal, a re-inspection will be required after audio issue is resolved.

###-#### - Damien
INSP-Final Inspection11/13/201911/14/201911/14/2019AFAIL
DetailsJim Page
City approved drawings have been notated areas that need to be corrected. Relocate dcevices that are overspaced or adjust candella setting. Provide weather proof devices in restrooms that have showers. Add notication in multi-person offices as dicussed.

5am
INSP-Final Inspection11/7/201911/7/201911/7/2019PPART
DetailsJim Page
Fire alarm inspection for surgical suite, southwest side of building complete to include corridors outside of surgical suite. Remaining areas to be inspected at a later date.

Phone #: ###-#### Inspection requested via web by Kristin Dolan
INSP-Final Inspection10/24/201910/24/201910/24/2019PFAIL
DetailsJim Page
Relocate smoke detectors that are to close to HVAC registers. Provide weather proof A/V devides in prep area behind surgical suites. Verify if door hold magnets are going to stay in place, if door holds stay then smoke detectors will be required for door release.

Phone #: ###-#### Inspection requested via web by Kristin Dolan
INSP-Final Inspection10/22/201910/23/201910/23/2019AFAIL
DetailsJim Page
Occupancy is a B occupancy, provide notification in post op and pre op rooms. Relocate notification in areas as discussed. No devices tested.

Call ahead to Damien @ ###-#### Phone #: ###-#### Inspection requested via web by Kristin Dolan