INSP-Final Inspection | 12/18/2019 | 12/18/2019 | 12/18/2019 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 12/17/2019 | 12/17/2019 | 12/17/2019 | P | CANC |
Troy Cobbley
|
|
|
Phone lines have been cut. Inspection requested via web by Morgan Ahten
|
INSP-Alarm Testing | 12/10/2019 | 12/11/2019 | 12/11/2019 | A | DONE |
Troy Cobbley
|
|
|
Head end equipment and interconnection with the fire sprinkler devices tested. For a final sign off we need the phone line troubles to report in less than 200 seconds, need elevator recall tested and final documents. Knox box needs installed as well.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Alarm Testing | 12/10/2019 | 12/10/2019 | 12/10/2019 | P | FAIL |
Troy Cobbley
|
|
|
We were unable to test phone lines due to non-functioning testing equipment. Inspection stopped since I can not verify communication means.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|