INSP-Final Inspection | 3/26/2020 | 3/27/2020 | 3/27/2020 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 3/24/2020 | 3/26/2020 | 3/26/2020 | P | FAIL |
Troy Cobbley
|
|
|
We finisher the inspection on elevator #2 but found that the power/control monitoring was not working and the sprinkler tamper switches are being reported as elevator smoke supervisory. All signals need to be reverified and the power monitoring repaired/tested.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 3/24/2020 | 3/24/2020 | 3/24/2020 | P | FAIL |
Troy Cobbley
|
|
|
Could not finish inspection due to the state elevator inspector tying up the second elevator. Will need to test this elevator and provide todays signal report.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 3/17/2020 | 3/18/2020 | 3/18/2020 | A | FAIL |
Troy Cobbley
|
|
|
Plan mods are need showing the actual means of communication. I noted missing Knox Box and unlabled dedicated circuit and a heat detector has been provided for elevator recall on exterior elevator door. No items tested or inspected.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|