Permit Information
Permit NumberFIR19-00358
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1835 W COMMERCE AVE
Project NameTRIMCO WAREHOUSE ADDITION
Customer Number 
ePlanReviewYes
Description
TVFP WILL INSTALL A COMPLETE AUTOMATIC DRY PIPE FIRE SPRINKLER SYSTEM THROUGHOUT THE NEW ADDITION PER NFPA 13 2016 FOR STORAGE. WORK WILL BEGIN AT THE CONNECTION TO THE EXISTING 8" MANIFOLD AND EXTEND THROUGH THE EXISTING UNHEATED WAREHOUSE TO THE NEW ADDITION.
NEW SPRAY BOOTH.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/7/20198/8/20198/8/2019APASS
DetailsJim Page
Final fire sprinkler inspection for area of work complete.

Mike O Phone #: ###-#### Inspection requested via web by Nathan Stenquist
INSP-Sprinkler Rough-in/Hydro7/26/20197/26/20197/26/2019PDONE
DetailsJim Page
Hydrostatic test for newly installed piping witnessed, no pressure loss observed.

Mike Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro7/24/20197/25/20197/25/2019ADONE
DetailsJim Page
24 hour air test has been witnessed, no pressure loss observed.

24 hour air test. Mike Phone #: ###-#### Inspection requested via web by Nathan Stenquist
INSP-Sprinkler Rough-in7/18/20197/18/20197/18/2019PPASS
DetailsJim Page
Rough in inspection for overhead fire sprinkler piping in area of work complete.

Mike Phone #: ###-####
INSP-Sprinkler Rough-in6/14/20196/17/20196/17/2019APART
DetailsJim Page
Inspection for pre-set hangers complete.

Hanger Attachments Rick Phone #: ###-#### Inspection requested via web by Nathan Stenquist