INSP-Final Inspection | 8/16/2019 | 8/16/2019 | 8/16/2019 | P | PASS |
Mark Scharfen
|
|
|
Tested and verified smokes/pulls and duct detectors. All speaker strobes functioned correctly. There is no hood installed in kitchen so point will need to be deleted off print and sent in as as build.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 8/13/2019 | 8/13/2019 | 8/13/2019 | P | FAIL |
Troy Cobbley
|
|
|
Plan modifications are needed showing all changes. Strobes need to be added in the large boys and girls restrooms and in all classrooms with the partial height walls. We set off the notification and I could not see a reasonable effect of the strobe mounted in the center of the room. Most of the areas checked there was no effect seen. Notification devices have been added to rooms, not all rooms are shown on the plans, smoke detectors are over spaced in three locations at the front lobby, fire smoke dampers are shown on the plans. Some strobes are blocked (kitchen), some are overspaced off walls and some 15cd exceed the 10' max ceiling height allowance. Also this inspection/permit sign off needs to follow the other FIR for the head end equipment sign off. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 8/9/2019 | 8/9/2019 | 8/9/2019 | P | FAIL |
Jim Page
|
|
|
Noted defecincies in multi purpose room located by the kitchen and in the kitchen area on city approved drawings, stopped inspection at kitchen due too the number of defecincies, notated issues that were inspected on the city approved drawing.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 8/8/2019 | 8/8/2019 | 8/8/2019 | P | CANC |
Troy Cobbley
|
|
|
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
|
INSP-Final Inspection | 8/5/2019 | 8/5/2019 | 8/5/2019 | P | CANC |
Troy Cobbley
|
|
|
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
|