INSP-Final Inspection | 8/13/2019 | 8/14/2019 | 8/14/2019 | A | PASS |
Jim Page
|
|
|
Previously noted items have been accepted, final fire sprinkler inspection complete for area of work.
This final has already been done, this is just the paper trail. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Conference | 8/6/2019 | 8/7/2019 | 8/7/2019 | A | DONE |
Troy Cobbley
|
|
|
Plans are in review status but I did note that several of the corridor sidewall heads appear to be blocked by adjacent walls and lockers.
George Jess is the contact. He would like this to take place before the hydro. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 8/6/2019 | 8/7/2019 | 8/7/2019 | A | PASS |
Troy Cobbley
|
|
|
The overhead hydro for the wet system was witnessed with no pressure loss. No rough-in inspection performed due to plans being in review status. George Jess is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Supply line flush | 7/23/2019 | 7/24/2019 | 7/24/2019 | P | DONE |
Jim Page
|
|
|
Underground main line flush complete.
George Jess is the contact for this Underground Hydro and Flush. Stacey @ Suez said he would be able to help us at 1PM. We appreciate your help with this. Thank you Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 7/23/2019 | 7/24/2019 | 7/24/2019 | P | DONE |
Jim Page
|
|
|
Hydrostatic test for undergound supply witnessed, no pressure loss observed.
George Jess is the contact for this Underground Hydro and Flush. Stacey @ Suez said he would be able to help us at 1PM. We appreciate your help with this. Thank you Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 7/2/2019 | 7/2/2019 | 7/2/2019 | P | PASS |
Troy Cobbley
|
|
|
Underground supply rough-in passed. Piping is ok for cover.
Bryan Collins is the contact. He would like this inspection as soon as possible today. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|