Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR19-00452
StatusFinaled
Name ALL VALLEY FIRE INSPECTIONS AND SER
Site Address 3390 N COLLISTER DR
Project NameThe Cottage New Fire Alarm
Customer Number 
ePlanReviewYes
Description
Scope of Work: Install new fire alarm. Relocate existing dialer to new FA. Low Frequency sounder bases are to be installed in the 15 resident rooms. 110 Candela strobes are to be installed in the 15 resident rooms at 25 inches below ceiling to top of strobe. The HVAC system is dedicated to PODs and none are over 2000cfm. Door holds to be re-used. All new wiring to be free-hung in attic using fire wire. The facilty is staffed 24/7/365.
This work does not appear to be associated with a building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/15/201910/17/201910/17/2019APASS
DetailsTroy Cobbley
Permit finaled. Previous corrections addressed.

Phone #: ###-#### Inspection requested via web by Jason Heath
INSP-Final Inspection10/10/201910/11/201910/11/2019PFAIL
DetailsJim Page
Audio visual devices in restrooms did not function. Smoke detector in room 6 is within 36 inches of HVAC register, relocate detector as discussed.

Phone #: ###-#### Inspection requested via web by Jason Heath