Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR19-00465
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 950 W BANNOCK ST Unit: 500
Project NameBanner Bank Ste 500 TI
Customer Number 
ePlanReviewYes
Description
**QUICK PERMIT** Ste 500- New tenant for entire 5th floor. Add 4 SSP, relocate 51 SSP and plug 29 SSP, all on Flexhead. Office light hazard
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/5/20199/5/20199/5/2019PPASS
DetailsJim Page
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Sprinkler Rough-in7/8/20197/9/20197/9/2019APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piiping complete, approved for cover. Notated city approved drawings in two areas, one has a head that needs relocated to the next tile to cover shadow area and an area that has 2 heads less than 6 foot apart. Will verify corrections at final inspection.

Phone #: ###-#### Inspection requested via web by Sam Ball