Permit Information
Permit NumberFIR19-00509
StatusFinaled
Name ALL VALLEY FIRE
Site Address 913 N LANDER ST
Project NameLander St Residence
Customer Number 
ePlanReviewYes
Description
Install a new fire sprinkler suppression system in a new residence per NFPA 13D.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/3/201910/4/201910/4/2019APASS
DetailsJim Page
Previously noted items have been corrected, irrigation shutdown was verified during waterflow. Final fire sprinkler inspection is complete.

Phone #: ###-#### Inspection requested via web by Jonathan LaFond
INSP-Final Inspection10/3/201910/3/201910/3/2019AFAIL
DetailsJim Page
Fire sprinkler head on riser has been painted, head needs replaced. Irrigation shutdown is not hooked up to flow switch, irrigation did not shut down on flow switch activation.

Phone #: ###-#### Inspection requested via web by Jonathan LaFond
INSP-Sprinkler Rough-in7/29/20197/30/20197/30/2019APASS
DetailsJim Page
All tenting in place at time of inspection, rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover. Sticker was placed on window for cover approval.

jeremy Phone #: ###-####
INSP-Sprinkler Rough-in7/17/20197/18/20197/18/2019APART
DetailsJim Page
Rough in inspection for overhead fire sprinkler piping complete, sprinkler piping between conditioned spaces approved for cover, piping in attic spaces that requires tenting will need to be inspected at a later date.

Jeremy Phone #: ###-####