Permit NumberFIR19-00583
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 3536 W HILL RD
Project NameHillside Jr. High Renovation
Customer Number 
ePlanReviewYes
Description
4,703 sq Ft. single level bldg renovation, Occupancy Class E, Construction Type V B.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/13/201911/13/201911/13/2019PPASS
DetailsJim Page
Final fire sprinkler inspection for area of work complete.

Contact Noemi Carrero ###-#### 30 min prior to Final Fire Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in9/24/20199/25/20199/25/2019APASS
DetailsJim Page
Previously noted items have been corrected, rough to cover inspection is complete, approved for cover.

Contact Noemi Carerro 208###-#### 30 min prior to RTC insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in9/23/20199/23/20199/23/2019PFAIL
DetailsJim Page
Sidewalls above ceiling grid in classroom 101 are more than 12 foot off of wall, heads are overspaced. Hardlids have been installed before rough in inspection has been performed, cover has not been approved. Mechanical room 114 has heads installed under duct work, still need heads above duct work 1 to 6 inches from bottom of deck, no fire sprinkler heads above duct work.

Contact Hunter Anderson ###-#### 30 min prior to RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank