INSP-Final Inspection | 12/11/2019 | 12/11/2019 | 12/11/2019 | P | CANC |
Troy Cobbley
|
|
|
Per note on the plans the existing fire alarm system will need to meet current code. I spoke to the contractor about the issue. No inspection performed.
Phone #: 4087506433 >> Inspection requested via mobile web by Josiah
|
INSP-Final Inspection | 12/4/2019 | 12/5/2019 | 12/5/2019 | A | FAIL |
Troy Cobbley
|
|
|
A plan modification is required showing the fire alarm panel that was installed previously without a permit.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
INSP-Sprinkler Rough-in/Hydro | 12/4/2019 | 12/5/2019 | 12/4/2019 | A | CANC |
Jim Page
|
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Wednesday, December 04, 2019.
|
INSP-Final Inspection | 11/15/2019 | 11/15/2019 | 11/15/2019 | P | FAIL |
Jim Page
|
|
|
Manufactures specs for fire panel requires the panel to be in an environment conditioned between 32 degrees fahrenheit to 120 degrees fahrenheit, provide conditioning in fire panel enclosure as discussed, conditioning has been provided for communicator encloser, heat detectors can remain in current location.
As early as possible Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
INSP-Final Inspection | 10/16/2019 | 10/16/2019 | 10/16/2019 | P | FAIL |
Troy Cobbley
|
|
|
No testing performed. Provide data that provide assurance that the new communicator will be maintained with-in the listed temperature range of 32 degrees to 120 degress. Also provide a smoke detector (heat may be ok) for the protection of the equipment as per NFPA 72. Drawing need to reflect the changes. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|