Information based on query as of Monday, June 24, 2024.
Permit Information
Permit NumberFIR19-00643
StatusIssued
Name APEX INTEGRATED SECURITY SOLUTIONS
Site Address 3304 LAKEHARBOR
Project NameEdgewater Aps Bldg N Cellular
Customer Number 
ePlanReviewYes
Description
Edgewater Apt Bldg N Cellular Installation Work is to add a Cellular Communicator on Building N to replace existing phone connection. PLAN MOD 12-10-19: Replace existing fire alarm panel. This change requires the entire system to meet current code compliance. This work is not associated with a building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/11/201912/11/201912/11/2019PCANC
DetailsTroy Cobbley
Per note on the plans the existing fire alarm system will need to meet current code. I spoke to the contractor about the issue. No inspection performed.

Phone #: 4087506433 >> Inspection requested via mobile web by Josiah
INSP-Final Inspection12/4/201912/5/201912/5/2019AFAIL
DetailsTroy Cobbley
A plan modification is required showing the fire alarm panel that was installed previously without a permit.

Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
INSP-Sprinkler Rough-in/Hydro12/4/201912/5/201912/4/2019ACANC
DetailsJim Page
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Wednesday, December 04, 2019.
INSP-Final Inspection11/15/201911/15/201911/15/2019PFAIL
DetailsJim Page
Manufactures specs for fire panel requires the panel to be in an environment conditioned between 32 degrees fahrenheit to 120 degrees fahrenheit, provide conditioning in fire panel enclosure as discussed, conditioning has been provided for communicator encloser, heat detectors can remain in current location.

As early as possible Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
INSP-Final Inspection10/16/201910/16/201910/16/2019PFAIL
DetailsTroy Cobbley
No testing performed. Provide data that provide assurance that the new communicator will be maintained with-in the listed temperature range of 32 degrees to 120 degress. Also provide a smoke detector (heat may be ok) for the protection of the equipment as per NFPA 72. Drawing need to reflect the changes. Phone #: 2088990672 >> Inspection requested via mobile web by Josiah