INSP-Final Inspection | 12/10/2019 | 12/11/2019 | 12/11/2019 | P | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, final fire sprinkler inspection is complete.
BRYAN Phone #: ###-####
|
INSP-Final Inspection | 12/4/2019 | 12/5/2019 | 12/5/2019 | A | FAIL |
Jim Page
|
|
|
Upright heads throughout space are painted, painted heads are not acceptable per NFPA13.
Damian Phone #: ###-####
|
INSP-Final Inspection | 12/3/2019 | 12/4/2019 | 12/4/2019 | A | FAIL |
Troy Cobbley
|
|
|
***Escutcheons painted in sounds rooms. Heads to close to sound baffles in sound rooms. MAS**
Damien Phone #: ###-####
|
INSP-Sprinkler Rough-in | 9/13/2019 | 9/16/2019 | 9/16/2019 | P | CANC |
Jim Page
|
|
|
**Inspection done on 9/16/2019*MAS**
Todd Phone #: ###-####
|
INSP-Sprinkler Rough-in | 9/16/2019 | 9/16/2019 | 9/16/2019 | P | PASS |
Jim Page
|
|
|
**Passed Above Ceiling. As built drawings needed before final inspection*MAS**
Todd Phone #: ###-####
|