Permit Information
Permit NumberFIR19-00681
StatusFinaled
Name JOHNSON CONTROLS FIRE PROTECTION
Site Address 4203 W STATE ST
Project NameValor Pointe Apartments
Customer Number 
ePlanReviewYes
Description
Valor Pointe Apartments - Provide and Install a new automatic and manual fire alarm system as shown on drawings. This work is associated with building permit BLD19-1828.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/31/20207/31/20207/31/2020PPASS
DetailsJim Page
Final fire alarm inspection is complete.
INSP-Final Inspection7/29/20207/30/20207/30/2020APART
DetailsJim Page
Fire alarm is compliamt with NFPA72, horns needed to be removed due too exceeding 110db. Plans are too be updated showing changes, permit can be finaled after cahnges are approved. 14 day TCO authorized pending fire alarm drawing update.

Coordinated with FA techician for 8AM, Brandon ###-####
INSP-Final Inspection7/29/20207/29/20207/29/2020PCANC
DetailsJim Page
Cancelled per conversation with point of contact, still troublshootoing area's were sound exceeds 110db.

SCREENED // James Phone #: ###-####
INSP-Final Inspection7/24/20207/27/20207/27/2020PFAIL
DetailsJim Page
Areas have been adjusted due too sound levels exceeding 110db, plans need to reflect corrections. Smoke detecotr to close to wall HVAC unit, minimum 36 inches away is required. Level 3 room sounder bases did not function with general fire alarm in common areas. Provide weather proof mounting boxes for bathrooms with showers. Inspection stopped after level 3 sounder bases did not function.

Phone #: ###-#### Inspection requested via web by Brandon Higley
INSP-Final Inspection7/22/20207/23/20207/23/2020PFAIL
DetailsJim Page
Provide small documents as discussed. Fire sprinkler monitoring is complete. Room notification did not function on general alarm.

Fire alarm inspection. Phone #: ###-#### Inspection requested via web by Ashley Chapman
INSP-Alarm Testing6/25/20206/29/20206/29/2020PCANC
DetailsTroy Cobbley
Please call our tech Brian ahead of time to verify start time ###-####. Contractor is Doug at ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by James Schofield Inspection cancelled from web by: James Schofield