INSP-Final Inspection | 7/31/2020 | 7/31/2020 | 7/31/2020 | P | PASS |
Jim Page
|
|
|
Final fire alarm inspection is complete.
|
INSP-Final Inspection | 7/29/2020 | 7/30/2020 | 7/30/2020 | A | PART |
Jim Page
|
|
|
Fire alarm is compliamt with NFPA72, horns needed to be removed due too exceeding 110db. Plans are too be updated showing changes, permit can be finaled after cahnges are approved. 14 day TCO authorized pending fire alarm drawing update.
Coordinated with FA techician for 8AM, Brandon ###-####
|
INSP-Final Inspection | 7/29/2020 | 7/29/2020 | 7/29/2020 | P | CANC |
Jim Page
|
|
|
Cancelled per conversation with point of contact, still troublshootoing area's were sound exceeds 110db.
SCREENED // James Phone #: ###-####
|
INSP-Final Inspection | 7/24/2020 | 7/27/2020 | 7/27/2020 | P | FAIL |
Jim Page
|
|
|
Areas have been adjusted due too sound levels exceeding 110db, plans need to reflect corrections. Smoke detecotr to close to wall HVAC unit, minimum 36 inches away is required. Level 3 room sounder bases did not function with general fire alarm in common areas. Provide weather proof mounting boxes for bathrooms with showers. Inspection stopped after level 3 sounder bases did not function.
Phone #: ###-#### Inspection requested via web by Brandon Higley
|
INSP-Final Inspection | 7/22/2020 | 7/23/2020 | 7/23/2020 | P | FAIL |
Jim Page
|
|
|
Provide small documents as discussed. Fire sprinkler monitoring is complete. Room notification did not function on general alarm.
Fire alarm inspection. Phone #: ###-#### Inspection requested via web by Ashley Chapman
|
INSP-Alarm Testing | 6/25/2020 | 6/29/2020 | 6/29/2020 | P | CANC |
Troy Cobbley
|
|
|
Please call our tech Brian ahead of time to verify start time ###-####. Contractor is Doug at ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by James Schofield Inspection cancelled from web by: James Schofield
|