INSP-Final Inspection | 7/17/2020 | 7/17/2020 | 7/17/2020 | P | PASS |
Jim Page
|
|
|
Final fire alarm inspection is complete.
Phone #: ###-#### Inspection requested via web by Robert Gobler
|
INSP-Final Inspection | 7/15/2020 | 7/15/2020 | 7/15/2020 | P | FAIL |
Jim Page
|
|
|
Smoke detectors are over spaced, add/relocate as discussed, plans will need to be revisedand submitted for corrections. Provide map showing initiating devices and place at FACP.
Phone #: ###-#### Inspection requested via web by Robert Gobler
|
INSP-Final Inspection | 7/10/2020 | 7/10/2020 | 7/10/2020 | P | FAIL |
Troy Cobbley
|
|
|
Need plan mods showing the communication method and the Sleeping area strobes need to meet NFPA 72 for the use of 110cd or 177cd as far as distance from ceiling as discussed. Need larger access to the east attic heat detector. Need the FACP shown upstairs instead of downstairs. Need to relocate or add a smoke detector in the basement as discussed. Plans show a PIV but none has been installed. See the city approved plans for corrections marked in red. No actual devices tested. Phone #: ###-#### Inspection requested via web by Robert Gobler
|