Permit Information
Permit NumberFIR19-00902
StatusFinaled
Name SENTRY SECURITY SYSTEMS
Site Address 6101 N PIERCE PARK LN
Project NameSolace House
Customer Number 
ePlanReviewYes
Description
Provide a full manual fire alarm system with sprinkler monitoring and low frequency sounder bases in sleeping rooms. System was engineered by E2CO. This work is associated with building permit BLD19-01649.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/17/20207/17/20207/17/2020PPASS
DetailsJim Page
Final fire alarm inspection is complete.

Phone #: ###-#### Inspection requested via web by Robert Gobler
INSP-Final Inspection7/15/20207/15/20207/15/2020PFAIL
DetailsJim Page
Smoke detectors are over spaced, add/relocate as discussed, plans will need to be revisedand submitted for corrections. Provide map showing initiating devices and place at FACP.

Phone #: ###-#### Inspection requested via web by Robert Gobler
INSP-Final Inspection7/10/20207/10/20207/10/2020PFAIL
DetailsTroy Cobbley
Need plan mods showing the communication method and the Sleeping area strobes need to meet NFPA 72 for the use of 110cd or 177cd as far as distance from ceiling as discussed. Need larger access to the east attic heat detector. Need the FACP shown upstairs instead of downstairs. Need to relocate or add a smoke detector in the basement as discussed. Plans show a PIV but none has been installed. See the city approved plans for corrections marked in red. No actual devices tested. Phone #: ###-#### Inspection requested via web by Robert Gobler