INSP-Final Inspection | 7/2/2020 | 7/2/2020 | 7/2/2020 | P | PART |
Jim Page
|
|
|
Final fire sprinkler inspection for TCO phase 1 complete.
Richard Clark is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Final Inspection | 6/30/2020 | 7/1/2020 | 7/1/2020 | P | CANC |
Troy Cobbley
|
|
|
Not ready for final. Richard Clark is the contact. Thanks! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in | 6/30/2020 | 7/1/2020 | 7/1/2020 | A | CANC |
Troy Cobbley
|
|
|
Per Richard this inspection is not needed. Intent was for turning on underground water supply.
underground_Richard *screend* Phone #: ###-####
|
INSP-Final Inspection | 6/30/2020 | 7/1/2020 | 6/30/2020 | A | CANC |
Jim Page
|
|
|
Richard Clark is the contact. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Sprinkler Rough-in | 6/19/2020 | 6/22/2020 | 6/22/2020 | A | FAIL |
Jim Page
|
|
|
Upright coverage in Board Room around partition wall is overspaved, partition wall framing goes all the wat too deck, correct uprigh coverage issue. Office B131 has upright overspacing issues, correct spacing to be compliant with NFPA13. Fire sprinkler head in east main entry is painted, replace painted head. Pendant heads in northeast main entry area with be hit by cabinet dooes in current locaiton, sprinkler heads in front of cabinets will need to be relocated, inspection stopped, a full rough in with exception to hardlids will need to be completed.
Jim Baker is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 4/29/2020 | 4/30/2020 | 4/30/2020 | P | CANC |
Jim Page
|
|
|
Inspection request cancelled per conversation with point of contact, point of contact noticed overspacing issues with walls that go to the deck causing upright coverage issues, inspection will be rescheduled for a later date.
Richard Clark is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|