INSP-Final Inspection | 6/18/2020 | 6/18/2020 | 6/18/2020 | P | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection is complete.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in/Hydro | 4/8/2020 | 4/9/2020 | 4/9/2020 | P | DONE |
Jim Page
|
|
|
Hydrostaic test for overhead fire sprinkler piping has been witnessed, no pressure loss observed at riser provided gauge.
Hydrostatic test Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 3/19/2020 | 3/20/2020 | 3/20/2020 | A | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, all tenting in place at time of inspection, cover is approved. Approval sticker has been placed.
Call James when heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 3/19/2020 | 3/19/2020 | 3/19/2020 | P | FAIL |
Jim Page
|
|
|
Level 1 kitchen and hallway, hallway head does not extend past the corner of wall as shown on city approved drawings, due to head not being past the wall the kitchen heads in 2 units are overspaced, inspection stopped.
Overhead rough ; tenting, call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|