INSP-Final Inspection | 2/11/2020 | 2/12/2020 | 2/12/2020 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
INSP-Final Inspection | 2/6/2020 | 2/7/2020 | 2/6/2020 | A | CANC |
Troy Cobbley
|
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Thursday, February 06, 2020.
|
INSP-Final Inspection | 2/5/2020 | 2/6/2020 | 2/6/2020 | A | FAIL |
Greg Ruxton
|
|
|
Permit failed based on noted deficiencies: induct smoke detector descriptors need to be corrected in Bld 1 and 2; Blding 2 office duct detector discriptor identified device as being in building 4; contractor to check all induct smoke detectors descriptors in B 1 and 2 for accuarcy before next inspection; B2 4th floor riser room inaccessible due to malfunctioning lock on door; B1 basement riser room device descriptors to identify location of devices in basement; B4 basement pull station descriptor identifies device being on 1st floor; B3 notification appliances on 1st floor near main lobby not in synch.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Froese
|