Permit Information
Permit NumberFIR20-00072
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 1666 S ENTERTAINMENT AVE
Project NameCosta Vida TI
Customer Number 
ePlanReviewYes
Description
Remodel existing restaurant building for new Costa Vida tenant. Upgrade remaining area of building to OH2 for future tenant options.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/3/20208/3/20208/3/2020PPASS
DetailsTroy Cobbley
Permit finaled.

Phone #: ###-#### Inspection requested via web by Brian Carlisle
INSP-Sprinkler Rough-in/Hydro7/28/20207/29/20207/29/2020APASS
DetailsTroy Cobbley
Rough-in and overhead hydro witnessed. Piping is ok for cover.

Phone #: ###-#### Inspection requested via web by Brian Carlisle
INSP-Final Inspection7/27/20207/27/20207/27/2020PCANC
DetailsTroy Cobbley
Phone #: ###-#### Inspection requested via web by Brian Carlisle
INSP-Sprinkler Rough-in7/27/20207/27/20207/27/2020PPASS
DetailsTroy Cobbley
The combustible concealed space above the cooler has been filled with insulation. The area is ok for cover.

Look at insulation above cooler. Phone #: ###-#### Inspection requested via web by Brian Carlisle
INSP-Sprinkler Rough-in7/17/20207/17/20207/17/2020PDONE
DetailsTroy Cobbley
The space above the cooler will need to meet one of the exceptions in NFPA 13 8.15 to delete coverage or sprinklers will need to be added.

Cooler room outside changed we had them fill with insulation need check it out before they cover. Phone #: ###-#### Inspection requested via web by Brian Carlisle
INSP-Sprinkler Rough-in6/24/20206/25/20206/25/2020APASS
DetailsTroy Cobbley
Piping above the hard lid in hall is ok for cover.

Phone #: ###-#### Inspection requested via web by Brian Carlisle
INSP-Sprinkler Rough-in6/24/20206/25/20206/24/2020PCANC
DetailsTroy Cobbley
Hard lids Phone #: ###-#### >> Inspection requested via web by Brian Carlisle Inspection cancelled from web by: Brian Carlisle