Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR20-00103
StatusFinaled
Name PROTEX
Site Address 1175 W LAKE HAZEL RD
Project NameOld Dominion TI
Customer Number 
ePlanReviewYes
Description
Add Fire alarm extender panel for additional notification. This work is associated with building permit BLD19-00708.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/13/20205/13/20205/13/2020PPASS
DetailsTroy Cobbley
Permit finaled.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection5/7/20205/8/20205/8/2020AFAIL
DetailsTroy Cobbley
Need monitor modules installed and as-builts showing the installation of the monitor modules for the trouble signals from the dry pipe sprinkler system accelerators. Per tech they worked wednesday. This piece of equipment needs to be monitored per IFC 903.4. Also need the map updated showing all initiating devices. Need NFPA 72 Record of Completion.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection4/16/20204/17/20204/17/2020AFAIL
DetailsTroy Cobbley
The office area ceiling mounted strobes are overspaced. The truss mounted strobes in the warehouse area are overspaced. No testing performed. Need ceiling installed in the NAC panel room so the smoke detector works.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection4/16/20204/17/20204/16/2020ACANC
DetailsTroy Cobbley
Contact is Dan. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten