Permit Information
Permit NumberFIR20-00139
StatusFinaled
Name WEBSTER FIRE PROTECTION
Site Address 5015 N PIERCE PARK LN
Project NamePierce Park Elementary
Customer Number 
ePlanReviewYes
Description
New fire alarm system for a new school, includes manual fire alarm, waterflow monitoring and occupant notification. This work is associated with building permit BLD19-00248.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/30/20207/31/20207/31/2020APASS
DetailsTroy Cobbley
verified function of the new voice evac hand set.

ermit finaled. Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster
INSP-Final Inspection7/29/20207/30/20207/30/2020ACANC
DetailsJim Page
Inspection ws suppose to be scheduled for 31JULY2020 per conversation with point of contact, this request is cancelled.

Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster
INSP-Final Inspection5/19/20205/20/20205/20/2020APART
DetailsJim Page
Inpsection complete per NFPA72, city approved drawings to be updated for minor corrections before permit can be finaled. Possible addition of EVS-LOC in office area to be added to city approved drawings and installed at a later date. Fire alarm is complete for 90 day TCO.

Phone #: ###-#### Inspection requested via web by Ken Webster: Coordinated for 9AM with Jim Page
INSP-Final Inspection5/18/20205/19/20205/19/2020PCANC
DetailsJim Page
Rescheduled for 20MAY2020 for completion of walkthrough items, this request is cancelled.

Phone #: ###-#### Inspection requested via web by Ken Webster
INSP-Final Inspection5/19/20205/19/20205/19/2020ACANC
DetailsJim Page
Phone #: ###-#### Inspection requested via web by Ken Webster: Coordinated for 9AM with Jim Page
INSP-Final Inspection5/19/20205/19/20205/19/2020ACANC
DetailsJim Page
Inpsection request was for a conference, this request is cancelled.
INSP-Conference5/19/20205/19/20205/19/2020ADONE
DetailsJim Page
Performed walkthrough, items noted are: Strobes in gym lobby show 30cd on city approved plans, ceiling exceeds 20 feet, strobes will have to be increased. Nurses station strobe is overspaced plus one will need to be added for laydown area coverage. Kitchen hood causes coverage issues in kitchen area, stobe will need to be added for proper coverage. Device in mail room is overspaced, candela will need to be increased for proper coverage or relocate device. East corridor by stairs exceeds 20 feet, candela setting at 30cd does not provide proper coverage, candella will be increased to 75cd. Items noted will need to be reflected on city approved drawings before permit can be finaled.
INSP-Alarm Testing4/6/20204/7/20204/7/2020APART
DetailsJim Page
Fire alarm testing is complete, fire sprinkler riser monitoring is tested/active.

clear // buck tom Phone #: ###-####
INSP-Final Inspection4/3/20204/6/20204/6/2020AFAIL
DetailsTroy Cobbley
No inspection test reports, flow switches and tampers are unhooked and when hooked back up there is a trouble signal also missing a resistor. No testing done. Inspection stopped.

cleared // Buck Phone #: ###-####