Permit Information
Permit NumberFIR20-00162
StatusIssued
Name JOHNSON CONTROLS FIRE PROTECTION SE
Site Address 3730 W QUAIL HOLLOW CT
Project NameQuail Hollow Court
Customer Number 
ePlanReviewYes
Description
**QUICK PERMIT** Quail Hollow Court - This is a remodel of an existing residence that was originally constructed with fire sprinklers in 2005. Originally there was an exterior porch area that was not protected. Adjacent to the porch was a corridor with two sprinklers. When the porch was remodeled it became an enclosed area and the corridor wall between the porch and the corridor went away. Now the heads in the corridor are over spaced to protect the remodeled area. This scope is to relocate the sprinklers to match the existing rooms on either side as shown on the plans. The spacing will be the same as the other two rooms. New sprinklers will be used of the same brand, type, and model as the rest of the residence. The remote area for this structure was at the top floor of the two story building. The work referenced takes place on the first floor. No hydraulic calculations have been created or submitted. This work involves moving two existing sprinklers less than 3 feet.

Residence,
Two sprinklers total
NFPA 13 D
No hydraulic calculations
Sprinkler head submittal
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in3/11/20203/12/20203/12/2020PPASS
DetailsJim Page
Rough to cover inspection for area of work is complete, area of work is approved for cover. Ceiling fan is installed in front of the fire place, sprinkler head next to fan is less than 3 foot away, if fan remains then sprinkler head must comply with 8.2.5 of the 2016 NFPA13D. Annual inspection on fire sprinkler system as well as backflow inspection will be required before this scope of work can be finaled.

christin Phone #: ###-####