Permit Information
Permit NumberFIR20-00313
StatusIssued
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 5892 N FIVE MILE RD
Project NameNorthview Apartments 24-Plex
Customer Number 
ePlanReviewYes
Description
Shilo will install a new fire sprinkler system into the new 24-Plex per NFPA 13R, 2016, and the City of Boise.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/10/20208/11/20208/11/2020PCANC
DetailsTroy Cobbley
Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection8/7/20208/10/20208/10/2020PCANC
DetailsTroy Cobbley
Cancel per Gabe.

Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection8/6/20208/7/20208/7/2020PCANC
DetailsTroy Cobbley
The fire alarm contractor did not schedule a final yet. No inspection performed.

Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro8/4/20208/5/20208/5/2020APASS
DetailsTroy Cobbley
The overhead hydros for the first, second and third floors witnessed with no pressure loss at the guages.

Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro7/29/20207/30/20207/30/2020ACANC
DetailsTroy Cobbley
To be rescheduled for tomorrow per Gabe Garduno is the contact. Thanks so much! (: Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in7/20/20207/20/20207/20/2020PPASS
DetailsTroy Cobbley
The tenting passed for the two west most third floor apartments. Piping is ok to cover.

Matt - screened Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro7/15/20207/16/20207/16/2020APASS
DetailsTroy Cobbley
The two apartments on west side of breezeway piping is ok for cover. Tenting passed.

screened // Matt Phone #: ###-#### **Rescheduled by JHB to 7/16. Matt requested to have inspection performed at 7:30am / as early as possible.
INSP-Sprinkler Rough-in6/25/20206/26/20206/26/2020APASS
DetailsTroy Cobbley
The two apartments, third floor, east side of breeze way, tenting is passed. Piping can be covered.

Matt ..... screened Phone #: ###-####
INSP-Sprinkler Rough-in6/18/20206/19/20206/19/2020APASS
DetailsTroy Cobbley
The two third floor east most apartments tenting has been repaired. Piping is ok for cover.

Matt *screened* Phone #: ###-####
INSP-Sprinkler Rough-in6/17/20206/17/20206/17/2020PFAIL
DetailsTroy Cobbley
tenting still not repaired. No cover for third floor cover.

Matt Phone #: ###-####
INSP-Sprinkler Rough-in6/16/20206/17/20206/17/2020APART
DetailsTroy Cobbley
The first and second floors, very east end, all piping is ok for cover. Third floor tenting failed and piping can not be covered.

Gabe Garduno is the contact. Thanks so much! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in6/11/20206/12/20206/12/2020APASS
DetailsTroy Cobbley
The sprinkler rough-in passed for the six east most apartments. Piping can be covered except for the third floor which does not have tenting yet.

Gabe Garduno is the contact. (: Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in6/1/20206/2/20206/2/2020APASS
DetailsTroy Cobbley
The four pendants have been relocated and the two sidewall heads have been added at the first floor intermediate stair landings. Basically the 18 east most apartments rough-ins are passed. The first and second floor piping can be covered. The third floor piping can not be covered until a tenting inspection has been passed. Cam Hess is the contact Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in6/1/20206/1/20206/1/2020PCANC
DetailsTroy Cobbley
Gabe Garduno is the contact Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in5/29/20206/1/20206/1/2020APART
DetailsTroy Cobbley
Todays inspection was for the three groups of six apartments starting from the east end. Rough-in passed but four pendant needs to be relocated as discussed. Two sidewall heads need to be installed, per plan, under the intermediate laddings as discussed. Piping at the fur down in these three groups of six can be covered. No piping on the third floor can be covered until a tenting inspection has been passed. Cam is going to provide as-builts with the additional 90's included in calcs as discussed and the possible deletion of heads at the landings.

Cam Hess is the contact (: Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in5/21/20205/22/20205/22/2020APART
DetailsTroy Cobbley
The second floor fur downs on the east half of the building are ok for cover. I discussed with Pat the need to have blocks of six as previously agreed ready to inspect. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in5/15/20205/15/20205/15/2020PPART
DetailsTroy Cobbley
The sprinkler piping above the soffit/hard lids on second floor is ok for cover.
INSP-Sprinkler Rough-in5/12/20205/13/20205/13/2020AFAIL
DetailsTroy Cobbley
First and second floors on the east end apartments need additional hangers. Third floor east end apartments need plan mods showing the actual piping routing. No approval for cover.

Gabe Garduno is the contact. This will be a partial Rough-In inspection. Thanks! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection8/11/20208/14/2020 A 
DetailsJim Page
Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus